Wire / Cable

Applicable Standard

IS 694, BS 6004, BS 2465

Type & Size

Single Core - sheathed / unsheathed from 0.5 sqmm.
Multi Core - from 0.5 sqmm to 4 sqmm.

Construction

Conductor

Insulation

Inner Sheath

Outer Sheath

 

Applications

Solid / Stranded / Flexible.

PVC general Purpose Heat Resistance (HR) Flame-Retardant Low Smoke (FRLS)

PVC general purpose Heat Resistance (HR)

Flame Retardant Low Smoke (FRLS)

Zero Halogen Fire Retardant (ZHFR)

Low Smoke Zero Halogen (LSZH)

Control panels, machinery, building wiring, household wiring, etc

Plain Copper Conductor PVC Insulated Un-Sheathed 1100v Single core cable for Panel board wiring.

Area in Sq. mm. Conductor construction Bunch dia in mm approx. Max DC resistance ohm/km at 20° C Insulation thickness nominal mm. Cable dia approx mm. Current rating in Amp.
0.50 16/0.2 0.94 39.00 0.6 2.2 4
0.75 24/0.2 1.20 26.00 0.6 2.5 7
1.00 32/0.2 1.34 19.50 0.6 2.6 11
1.50 48/0.2 1.64 13.30 0.6 2.9 14
2.50 80/0.2 2.08 7.98 0.7 3.5 19
4.00 56/0.2 2.61 4.95 0.8 4.3 26

Plain Copper Conductor PVC Insulated and Sheathed 1100v Multi-core Flexible cables.

Conductor area sq.mm Construction no. / dia Cond. Dia mm Max. DC resistance Ohm / km at 20° C Insu. Thickness nominal mm Core dia mm Sheathed thickness in mm nominal Overall Dia in mm Approx. Current rating Amp
            2C 3C 4C 2C 3C 4C  
0.50 16/0.2 0.94 39.0 0.6 2.2 0.9 0.9 0.9 6.2 6.6 7.2 4
0.75 24/0.2 1.20 2.06 0.6 2.5 0.9 0.9 0.9 6.8 7.2 7.9 7
1.00 32/0.2 1.34 19.50 0.6 2.6 0.9 0.9 0.9 7.0 7.5 8.1 11
1.50 48/0.2 1.64 13.30 0.6 2.9 0.9 0.9 1.0 7.6 8.1 9.0 14
2.50 80/0.2 2.08 7.98 0.7 3.5 1.0 1.0 1.0 9.0 9.6 10.5 19
4.00 56/0.2 2.61 4.95 0.8 4.3 1.0 1.0 1.0 10.6 11.3 12.4 26